How to setup KNX Flags to update BACnet Values properly in MAPS

06 Feb 2023

This article describes the reason and gives a work around when the values on BACnet or Modbus doesn´t change...

 

APPLICABLE PRODUCTS

  • Intesis KNX Protocol Translators: (IN701KNX1000000, IN701KNX2500000, IN701KNX6000000, IN701KNX1K20000, IN701KNX3K00000).
     

PRE-REQUISITES

eLearning course Intesis MAPS to learn the secrets of Intesis MAPS.

 

ISSUE/PROBLEM

When trying to map objects in Intesis MAPS, it may happen that you do not see any updates on the BACnet or Modbus side, however you have changed the values on the KNX side.

 

POSSIBLE CAUSES / ANSWER

There might be these missing flags (U and W) to get the correct status, which is marked in red square in the MAPS image below:

 

U, the object can be updated from KNX after power failure.
W, the object can be written from KNX.

 

ADDITIONAL INFO

To know more about how to use the Intesis MAPS configuration tool, check out our Intesis MAPS eLearning courses

© HMS Networks AB 2023