This article explains the steps to perform a factory reset of an Intesis V6 gateway. Gateways using this hardware can be factory reset by powering on the device while holding down the A and B buttons.
APPLICABLE PRODUCTS
Intesis gateways under the V6 hardware:
Intesis 700 Series Network (Protocol Converters): IN7004851000000, IN7004852500000, IN7004856000000, IN7004851K20000, IN7004853K00000, IN701KNX1000000, IN701KNX2500000, IN701KNX6000000, IN701KNX1K20000, IN701KNX3K00000, IN703DAL0640000, IN704DAL1280000
Intesis Protocol Converters (legacy):
- Modbus: INMBSDAL0640200, INMBSDAL1280200, INMBSMEB0100000, INMBSMEB0200000, INMBSMEB0600000, INMBSMEB1200000, INMBSBAC1000000, INMBSBAC2500000, INMBSBAC6000000, INMBSBAC1K20000, INMBSBAC3K00000, INMBSKNX1000000, INMBSKNX2500000, INMBSKNX6000000, INMBSKNX1K20000, INMBSKNX3K00000
- KNX: INKNXDAL0640200, INKNXMEB0100000, INKNXMEB0200000, INKNXMEB0600000, INKNXMEB1200000, INKNXMBM1000000, INKNXMBM2500000, INKNXMBM6000000, INKNXMBM1K20000, INKNXMBM3K00000, INKNXBAC1000000, INKNXBAC2500000, INKNXBAC6000000, INKNXBAC1K20000, INKNXBAC3K00000
- BACnet: INBACDAL0640200, INBACDAL1280200, INBACMEB0100000, INBACMEB0200000, INBACMEB0600000, INBACMEB1200000, INBACMBM1000000, INBACMBM2500000, INBACMBM6000000, INBACMBM1K20000, INBACMBM3K00000, INBACKNX1000000, INBACKNX2500000, INBACKNX6000000, INBACKNX1K20000, INBACKNX3K00000
- ASCII: INASCBAC6000000, INASCBAC3K00000, INASCKNX6000000, INASCKNX3K00000
Intesis HVAC gateways (legacy):
- Fujitsu: INMBSFGL016O000, INKNXFGL016O000
- Hitachi: INMBSHIT016O000, INKNXHIT016O000, INBACHIT016O000, INMBSHIT064O000, INKNXHIT064O000, INBACHIT064O000
- Hisense: INMBSHIS016O000, INKNXHIS016O000, INBACHIS016O000, INMBSHIS064O000, INKNXHIS064O000, INBACHIS064O000
- Midea: INBACMID004O000
- Mitsubishi Electric: INMBSMIT050C000, INKNXMIT050C000, INMBSMIT100C000, INKNXMIT100C000
- Panasonic: INMBSPAN016O000, INKNXPAN016O000, INBACPAN016O000, INMBSPAN064O000, INKNXPAN064O000, INBACPAN064O000, INMBSPAN128O000, INBACPAN128O000
- Samsung: INMBSSAM004O000, INKNXSAM004O000, INBACSAM004O000, INMBSSAM008O000, INKNXSAM008O000, INBACSAM008O000, INMBSSAM016O000, INKNXSAM016O000, INBACSAM016O000, INMBSSAM064O000, INKNXSAM064O000, INBACSAM064O000
PRE-REQUISITES
Physical access to the Intesis gateway.
FACTORY RESET PROCEDURE
- Power off the Intesis gateway.
- Press and hold both A and B buttons.
- Power the Intesis gateway on.
- Continue holding the buttons for about 10 seconds until the LEDs cycle from top to bottom, then from bottom to top.
- Release the buttons.
- All LEDs will cycle up and down then down and up again for about 20 seconds. Once the process is complete, all LEDs will blink.