Tank Fill App: CUB5P, CUB5I, CUB5V

12 Aug 2026

Tank Fill App:    CUB5P, CUB5I, CUB5V

 

Description text that describes what the information in this article is related to. Make sure that the text includes the product name and the summary of the issue the article solves in the first 120 characters (Mandatory)

 

APPLICABLE PRODUCT MODELS

CUB5PR00 - CUB5PB00

CUB5IR00 - CUB5IB00

CUB5VR00 - CUB5VB00 

PRE-REQUISITES

The CUB5P has an internal jumper that needs to be set to the correct input signal value.

The CUB5I has 4 different internal inputs that need to be set per the input signal.

The CUB5V has an internal jumper that needs to be set to the correct input signal value.

IN THIS ARTICLE (Mandatory)

ITEM 1

Table of content

  1. Determine the type of input signal being used and set the internal jumper accordingly.
  2. Program the Input parameters in Module #1-INP
  3. Programming any Setpoint output devices required in Module 4-SPT
  4. Program the Serial output in Module #5-SER if required.

 

  1. Instructions for Step 1:

Set the internal jumpers per the instructions for each display.

          CUB5P                                CUB5I                               CUB5V

    

 

Instructions for Step 2:

Press and hold the SEL button until you see Pro No

Press RST button once to see 1-INP

Continue pressing SEL button to see RANGE = (select the correct input range)

Continue pressing SEL to see DECPT = (select number of decimals in your display)

Continue pressing SEL to see OFSET = usually left at ZERO

Continue pressing SEL to see FILTR = 1

Continue pressing SEL to see BAND = 120

Continue pressing SEL to see STYLE = KEY

Continue pressing SEL to see INP-1 = 4.00 (if using a current input signal)

Continue pressing SEL to see DSP-1 = 0

Continue pressing SEL to see INP-2 = 20.00 (if using a current input signal)

Continue pressing SEL to see DSP-2 = 100 (or what your MAX signal will display)

Continue pressing SEL to see USR IN = NO

Continue pressing SEL to see Pro No

Continue pressing SEL to see END.

 

Instructions for Step 3:

Press and hold the SEL button until you see Pro No

Press RST button 4 times to see 4-SPT

Continue pressing SEL to see SPSEL = NO (press RST to change to SP-1)

Continue pressing SEL to see ENB-2 = NO

Continue pressing SEL to see ACT-1 = HI-UB

Continue pressing SEL to see SPT-1 = (your setpoint value)

Continue pressing SEL to see HYS-1 = 2

Continue pressing SEL to see TON-1 = 0.0

Continue pressing SEL to see TOF-1 = 0.0 Continue pressing SEL to see RST-1 = AUTO

Continue pressing SEL to see REN-1 = YES

Continue pressing SEL to see STB-1 = NO

Continue pressing SEL to see CHC-1 = NO

Continue pressing SEL to see Pro No

Continue pressing SEL to see END

 

Instructions for Step 4:

Press and hold the SEL button until you see Pro No

Press RST button 5 times to see 5-SER

Continue pressing SEL to see BAUD = 9600

Continue pressing SEL to see DATA = 7-bit

Continue pressing SEL to see PAR = Odd

Continue pressing SEL to see ADDr = 00

Continue pressing SEL to see ABBr = NO

Continue pressing SEL to see OPT = NO

Continue pressing SEL to see Pro No

Continue pressing SEL to see END.

 