BACnet 802.3 Master

08 May 2026

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT 

 

APPLICABLE PRODUCTS

  • All Products Using Crimson 2.0 or Crimson 3.0 BACnet Slave Drivers 
  • G3 Series of HMI
  • Data Station Plus Series and Modular Controller Series 

 

PRE-REQUISITES 

  • Crimson 2.0 Build 2.0.0.324 and Later
  • All Builds of Crimson 3.0 and up 
  • BACnet Version 1, Revision 5 

 

IN THIS ARTICLE 

The products are advanced data-management devices that perform protocol conversion and data logging, and also provide a web-based virtual HMI facility. The G3 HMI products combine this functionality with color touchscreens for local viewing. The products support BACnet slave and master modes, over MS/TP, 802.3 and UDP/IP. 

*While BACnet is a peer-to-peer protocol, the Red Lion Controls implementation configures as a Master (client) or Slave (server).

 

BACNET STANDARDIZED DEVICE PROFILE (ANNEX L)  

  • B-ASC    BACnet Application Specific Controller 
  •  B-SS      BACnet Smart Sensor 
  • B-SA       BACnet Smart Actuator 

 

BACNET INTEROPERABILITY BUILDING BLOCKS SUPPORTED (ANNEX K)

 

  •  DS-RP-B         Data Sharing, Read Property, B 
  •  DS-RPM-B      Data Sharing, Read Property Multiple, B 
  •  DS-WP-B        Data Sharing, Write Property, B 
  •  DM-DDB-B     Device Management, Dynamic Data Binding, B
  •  DM-DOB-B     Device Management, Dynamic Object Binding, B
  •  DM-DCC-B     Device Management, Device Communication Control, B 
  •  DM-RD-B       Device Management, Reinitialize Device, B

     

    STANDARD OBJECT TYPES

      The following object types are supported…  

    • Analog Input, Analog Output, Analog Value 

     • Binary Input, Binary Output, Binary Value  

    • Device 

     

    The following conditions apply to all object types… 

     • Objects may be neither dynamically created nor deleted. 

     • No proprietary properties are implemented. 

    • No properties may be written unless required by the BACnet specification.  

    • No properties have range restrictions beyond those in the BACnet specification. 

     

    The only optional properties support are on the Device object and are as follows…  

    • Local Time  

    • Local_Date  

     

    SEGMENTATION CAPABILITY 

     Segmentation is not supported. 

     

     DATA LINK LAYER OPTIONS 

     

  • BACnet IP (Annex J)
  • ISO 8802-3 Ethernet (Clause 7) 
  • MS/TP Master (Clause 9) at 9600, 19200, 38400 and 78400 Baud. 
  • MS/TP Slave (Clause 9) at 9600, 19200, 38400 and 78400 Baud.  

 

   DEVICE ADDRESS BINDING 

 Static address binding is not supported.  

 

 NETWORKING OPTIONS 

 No networking options are supported.  

 

CHARACTER SETS SUPPORTED 

  • ANSI X3.4 

     

GATEWAY FUNCTIONALITY 

 

  • The BACnet implementation is capable of exposing, and accepting writes to, any data items gathered from communications devices compatible with the Crimson runtime software. Data items may be exposed as any of the standard analog or binary object types. The list of available drivers is available from HMS Networks - Hardware Meets Software™ | Industrial ICT website. 

HMS Networks Support 

 https://support.hms-networks.com/

 

© HMS Networks AB 2026