Take the complexity out of the integration process: Create your project with a predefined template, configure the needed parameters, enable the desired signals, and check the communication between the gateway and the system.
Language
Samsung to BACnet/IP & MS/TP - Up to 16 Indoor Units
Item number IN770AIR00SO000
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 16 indoor units from a single interface.
The interface supports both BACnet/IP and BACnet MS/TP protocols.
Connection is simple, as the interface connects directly to the outdoor unit’s communication bus.
A scan function is available for automatic identification of the units present in the VRF system.
Signals assigned to the outdoor unit are available to be used in the integration.
Energy consumption signals from each indoor unit are available, so they can be checked individually.
This interface supports the WindFree™ Cooling technology and all the advantages it brings.
Templates can be imported and reused as often as needed, significantly reducing commissioning time.
Both the Intesis MAPS configuration tool and the interface's firmware can receive automatic updates.
Take the complexity out of the integration process: Create your project with a predefined template, configure the needed parameters, enable the desired signals, and check the communication between the gateway and the system.
Samsung to BACnet/IP & MS/TP - Up to 4 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 4 indoor units from a single interface.
Samsung to Home Automation - Up to 64 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a Home Automation system. The solution allows the integration of up to 64 indoor units from a single interface.
Panasonic to Home Automation - Up to 64 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a Home Automation system. The solution allows the integration of up to 64 indoor units from a single interface.
Replaced by: IN770AIR00SO000
This Hitachi application was designed to allow bidirectional control and monitoring of Hitachi VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allowed the integration of up to 16 indoor units from a single interface. Please refer to the new product reference for further details.
Fujitsu to BACnet/IP & MS/TP - Up to 64 Indoor Units
The Fujitsu application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 64 indoor units from a single interface.
Replaced by: IN770AIR00SO000
This Panasonic application was designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allowed the integration of up to 16 indoor units from a single interface. Please refer to the new product reference for further details.
Mitsubishi Heavy Industries to Home Automation - Up to 16 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a Home Automation system. The solution allows the integration of up to 16 indoor units from a single interface.
Panasonic to Modbus TCP/RTU - Up to 16 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 16 indoor units from a single interface.
Hitachi VRF systems to BACnet/IP & MS/TP Application - Up to 4 Indoor Units
The Hitachi application has been specially designed to allow bidirectional control and monitoring of Hitachi VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 4 indoor units from a single interface.
Mitsubishi Heavy Industries to Home Automation - Up to 4 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a Home Automation system. The solution allows the integration of up to 4 indoor units from a single interface.
Midea to BACnet/IP & MS/TP - Up to 4 Indoor Units
The Midea application has been specially designed to allow bidirectional control and monitoring of Midea Commercial and VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 4 indoor units from a single interface.
Hitachi to Modbus TCP/RTU - Up to 64 Indoor Units
The Hitachi application has been specially designed to allow bidirectional control and monitoring of Hitachi VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 64 indoor units from a single interface.
Samsung to KNX - Up to 4 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a KNX installation. The solution allows the integration of up to 4 indoor units from a single interface.
Mitsubishi Heavy Industries to Modbus TCP/RTU - Up to 16 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 128 indoor units from a single interface.
Midea to Modbus TCP/RTU - Up to 4 Indoor Units
The Midea application has been specially designed to allow bidirectional control and monitoring of Midea Commercial and VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 4 indoor units from a single interface.
Mitsubishi Heavy Industries to KNX - Up to 16 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a KNX installation. The solution allows the integration of up to 16 indoor units from a single interface.
Replaced by: IN770AIRXXSO000
This Samsung application was designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allowed the integration of up to 4 indoor units from a single interface. Please refer to the new product reference for further details.
Mitsubishi Heavy Industries to BACnet/IP & MS/TP - Up to 16 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 16 indoor units from a single interface.
Fujitsu to KNX - Up to 64 Indoor Units
The Fujitsu application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a KNX installation. The solution allows the integration of up to 64 indoor units from a single interface.
Mitsubishi Electric to Modbus TCP/RTU - Up to 50 groups
The Mitsubishi Electric application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Electric City Multi systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 50 groups from a single interface.
Replaced by: IN770AIR00SO000
This Hitachi application was designed to allow bidirectional control and monitoring of Hitachi VRF systems from a KNX installation. The solution allowed the integration of up to 16 indoor units from a single interface. Please refer to the new product reference for further details.
Mitsubishi Heavy Industries to Home Automation - Up to 128 Indoor Units
The Mitsubishi Heavy Industries application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Heavy Industries VRF systems from a Home Automation system. The solution allows the integration of up to 128 indoor units from a single interface.
Bosch to BACnet/IP & MS/TP - Up to 64 Indoor Units
The Bosch application has been specially designed to allow bidirectional control and monitoring of Bosch Air Flux and Mini-VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 64 indoor units from a single interface.
Replaced by: IN770AIR00SO000
This Panasonic application was designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allowed the integration of up to 16 indoor units from a single interface. Please refer to the new product reference for further details.
Replaced by: IN770AIRXXSO000
The Bosch-Modbus gateway allowed bidirectional communication between Bosch Commercial and VRF systems and Modbus RTU (RS-485) networks, bringing total control and supervision of the AC unit through its internal variables. Please refer to the new product reference for further details.
Midea to Modbus TCP/RTU - Up to 64 Indoor Units
The Midea application has been specially designed to allow bidirectional control and monitoring of Midea Commercial and VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 64 indoor units from a single interface.
Fujitsu to Home Automation - Up to 64 Indoor Units
The Fujitsu application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a Home Automation system. The solution allows the integration of up to 64 indoor units from a single interface.
Haier to KNX - 8 indoor units
The Haier-KNX gateway allows bidirectional communication between Haier Commercial and VRF systems and KNX installations. This communication brings total control of the AC unit from KNX, including monitoring of the AC unit’s internal variables, running hours counter (for filter maintenance control), and error codes.
Panasonic to KNX - Up to 64 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a KNX installation. The solution allows the integration of up to 64 indoor units from a single interface.
Samsung to Modbus TCP/RTU - Up to 4 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 4 indoor units from a single interface.
Replaced by: IN770AIR00MO000
This Hitachi application was designed to allow bidirectional control and monitoring of Hitachi VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or BACnet MS/TP client. The solution allowed the integration of up to 64 indoor units from a single interface. Please refer to the new product reference for further details.
Replaced by: IN770AIRXXSO000
This Samsung application was designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 4 indoor units from a single interface. Please refer to the new product reference for further details.
Panasonic to Modbus TCP/RTU - Up to 64 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 64 indoor units from a single interface.
Samsung to KNX - Up to 64 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a KNX installation. The solution allows the integration of up to 64 indoor units from a single interface.
Fujitsu to Modbus TCP/RTU - Up to 16 Indoor Units
The Fujitsu application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 16 indoor units from a single interface.
Fujitsu to Modbus TCP/RTU - Up to 4 Indoor Units
The Fujitsu application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 4 indoor units from a single interface.
Midea to Home Automation - Up to 4 Indoor Units
The Midea application has been specially designed to allow bidirectional control and monitoring of Midea Commercial and VRF systems from a Home Automation system. The solution allows the integration of up to 4 indoor units from a single interface.
Hitachi VRF systems to BACnet/IP & MS/TP Application - Up to 64 Indoor Units
The Hitachi application has been specially designed to allow bidirectional control and monitoring of Hitachi VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 64 indoor units from a single interface.
Samsung to Home Automation - Up to 16 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a Home Automation system. The solution allows the integration of up to 16 indoor units from a single interface.
Panasonic to KNX - Up to 4 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a KNX installation. The solution allows the integration of up to 4 indoor units from a single interface.
Replaced by: IN770AIR00MO000
This Hisense application was designed to allow bidirectional control and monitoring of Hisense VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allowed the integration of up to 64 indoor units from a single interface. Please refer to the new product reference for further details.
Samsung to Home Automation - Up to 4 Indoor Units
The Samsung application has been specially designed to allow bidirectional control and monitoring of Samsung NASA VRF systems from a Home Automation system. The solution allows the integration of up to 4 indoor units from a single interface.
Panasonic to Home Automation - Up to 16 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a Home Automation system. The solution allows the integration of up to 16 indoor units from a single interface.
Bosch to Home Automation - Up to 64 Indoor Units
The Bosch application has been specially designed to allow bidirectional control and monitoring of Bosch Air Flux and Mini-VRF systems from a Home Automation system. The solution allows the integration of up to 64 indoor units from a single interface.
Hisense to BACnet/IP & MS/TP - Up to 4 Indoor Units
The Hisense application has been specially designed to allow bidirectional control and monitoring of Hisense VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 4 indoor units from a single interface.
Replaced by: IN770AIR00SO000
The Bosch-Modbus gateway allowed bidirectional communication between Bosch Commercial and VRF systems and Modbus RTU (RS-485) networks, bringing total control and supervision of the AC unit through its internal variables. Please refer to the new product reference for further details.
Mitsubishi Electric to KNX - Up to 100 groups
The Mitsubishi Electric application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Electric City Multi systems from a KNX installation. The solution allows the integration of up to 100 groups from a single interface.
Panasonic to BACnet/IP & MS/TP - Up to 16 Indoor Units
The Panasonic application has been specially designed to allow bidirectional control and monitoring of Panasonic ECOi, PACi, ECOg / PAC, VRF systems from a BMS, SCADA, PLC, or any other device working as a BACnet/IP server or a BACnet MS/TP client. The solution allows the integration of up to 16 indoor units from a single interface.
Mitsubishi Electric to Modbus TCP/RTU - Up to 100 groups
The Mitsubishi Electric application has been specially designed to allow bidirectional control and monitoring of Mitsubishi Electric City Multi systems from a BMS, SCADA, PLC, or any other device working as a Modbus client. The solution allows the integration of up to 100 groups from a single interface.
Midea to Home Automation - Up to 16 Indoor Units
The Midea application has been specially designed to allow bidirectional control and monitoring of Midea Commercial and VRF systems from a Home Automation system. The solution allows the integration of up to 16 indoor units from a single interface.
Content of Delivery
Intesis Gateway, Installation Manual, USB Configuration cable.
Not Included (in delivery)
Power supply not included.
Net Width (mm)
106 mm
Net Height (mm)
58 mm
Net Depth (mm)
90 mm
Net Weight (g)
240 g
Mounting
DIN rail mount (bracket included), Wall mount
Input Voltage (V)
For DC: 12 .. 36 VDC ±10%, Max: 250 mA For AC: 24 VAC ±10 %, 50-60 Hz, Max: 127 mA Recommended voltage: 24 VDC, Max: 127 mA
Power Connector
3-pole
Operating Temperature °C Min
0 °C
Operating Temperature °C Max
60 °C
Housing Materials
Plastic
Packaging Material
Cardboard
Warranty (years)
3 years
Capacity
Up to 16 indoor units and up to 16 outdoor units.
Installation Conditions
This gateway is designed to be mounted inside an enclosure. If the unit is mounted outside an enclosure, precautions should always be taken to prevent electrostatic discharge to the unit. When working inside an enclosure (e.g., making adjustments, setting switches, etc.), typical anti-static precautions should always be followed before touching the unit.
CE
Yes
UL
Yes
WEEE Category
IT and telecommunications equipment
CB
Yes
UKCA
Yes
UKPSTI
Yes
BTL
Yes
ETIM Classification
EC001604
Connectors / Input / Output
Power supply, EIA-485, KNX, Ethernet, HVAC port, Binary inputs (dry contact), Console port USB.
Contains Battery
No
DIP & Rotary Switches
EIA-485 serial port configuration.
LED Indicators
Gateway and communication status.
Push Buttons
Factory reset. I-Am message (for BACnet only). Normal mode/programming mode switch (for KNX only).
Brand
Intesis
Country of Origin
Spain
HS Code
8517620000
Dual Usage
No
Export Control Classification Number (ECCN)
EAR99
Item Number
IN770AIR00SO000
Can't find a distributor or partner or need help to figure out which partner suits you?
No problem, you can always contact your nearest HMS office and let our sales and customer service staff take care of your enquiry.
To download this file you need to submit your email address. You will then get an email with the download link
Invalid email address
File | Product / versions | Filetype | Size | ||
---|---|---|---|---|---|
CAD Drawings 2D and 3D
|
zip | 4.2 MB |
90e6e605-22ce-6706-92f4-ff00001bbfd4
Download
|
||
Discover all you can do with this product. This document includes all the applications and their wiring diagrams.
|
Wiring Diagrams
|
1.5 MB |
3194d105-22ce-6706-92f4-ff00001bbfd4
Download
|
||
BACnet Protocol implementation conformance statement
|
BACnet Server PIC statement
|
1.0.1 | 97.4 KB |
e729d505-22ce-6706-92f4-ff00001bbfd4
Download
|
File | Product / versions | Filetype | Size | ||
---|---|---|---|---|---|
UKPSTI Certification
|
290.1 KB |
0c350be4-cb4a-45ed-9be5-5da029170f1b
Download
|
|||
CE Declaration of Conformity
|
197.8 KB |
8529d505-22ce-6706-92f4-ff00001bbfd4
Download
|
|||
BTL - 31015
|
BACnet Server Conformance Certificate - BTL
|
794.3 KB |
e3d4cd0b-4bc8-461f-894c-aec73369576a
Download
|
||
UK Declaration of Conformity
|
UKCA Declaration
|
241.7 KB |
402ad505-22ce-6706-92f4-ff00001bbfd4
Download
|
||
Listing Information (BTL-31015)
|
BACnet Server Testing Laboratories Product Listing
|
33.0 KB |
f2744a63-a739-4350-b046-6e77dc6ab937
Download
|
Installation guides
File | Product / versions | Filetype | Size | ||
---|---|---|---|---|---|
Installation Guide
|
2.0.3 | 1.6 MB |
f528d505-22ce-6706-92f4-ff00001bbfd4
Download
|
Manuals
File | Product / versions | Filetype | Size | ||
---|---|---|---|---|---|
Intesis MAPS User Manual
|
1.0.3 | 3.9 MB |
8e2ad505-22ce-6706-92f4-ff00001bbfd4
Download
|
||
User Manual
|
1.0.12 | 3.0 MB |
6e27d505-22ce-6706-92f4-ff00001bbfd4
Download
|
File | Product / versions | Filetype | Size | ||
---|---|---|---|---|---|
This application note includes recommendations to avoid polarity issues inRS485 networks.
|
Recommendations to avoid polarity issues
|
138.3 KB |
aa354a60-621b-441d-a24d-7ee1ceeff5f8
Download
|
||
This document describes how to estimate each indoor unit's energy consumption using Intesis 700 Series Air gateways, and its Power Estimation Algorithm.
|
Application note: The Power Estimation Algorithm.
|
7.1 MB |
0c128630-513a-4035-93e7-86108c616c9a
Download
|
The latest Intesis HVAC Compatibility Tool helps find the right gateway to integrate any HVAC system, by simply entering the brand and model. Users can also submit compatibility requests, so the information is updated regularly.
Training from HMS Academy reduces the total cost and time of your project and gives improved quality and efficiency of the solution.
HMS offers trainings related to products, technologies and more. This could be in the form of an onsite training, online training or by running one of our E-learning sessions.
Technical Services from HMS helps customers with any type of assistance needed in addition to the products bought from HMS. The Technical Services page offers a list of all services we provide.
The services are provided by HMS’ global team of skilled and experienced engineers who work together with you, providing various services.
Typical activities are project planning, setting up evaluation demos, creating and validating product configurations, providing guidance during field trials, and more.
Technical Services from HMS helps customers with any type of assistance needed in addition to the products bought from HMS. The Technical Services page offers a list of all services we provide.
The services are provided by HMS’ global team of skilled and experienced engineers who work together with you, providing various services.
Typical activities are project planning, setting up evaluation demos, creating and validating product configurations, providing guidance during field trials, and more.