Using the fieldbus configuration in Red Lion Workbench the RTU can be a Modbus master to the EtherTRAK-2 or E2 Modules. With Insert Master/Port within the Modbus Master protocol define the IP address of the I/O Module slave and port number. Define the station number, I/O Type, number of registers and declaration of variables with the Insert Slave/Data Block. Use the E2\E3 Address table or import the E2 I/O modules with the attached template project.
RTU Products:
ST-IPm-8460/VT-mIPm-248-D/VT-mIPm-138-D
I/O Products:
E2-MIX24880-D/E2-MIX24882-D/E2-MIX20884-D/E2-8AO20M-D/E2-32AI20M-D/E2-32AI10V-D/E2-32DI24-D/E2-32DO24-D/E2-16AI20M-D/E2-16AI-8AO-D/E2-16DI24-D/E2-16DIAC-D/E2-16DO24-D/E2-16DORLY-D/E2-16ISO20M-D/E2-16ISOTC-D/E2-10RTD-D
E3-MIX24882-1/E3-MIX24880-1/E3-MIX20884-1/E3-32DI24-1/E3-16DI24-1/E3-16DIAC-1/E3-32DO24-1/E3-16DO24-1/E3-16DORLY-1/E3-32AI20M-1/E3-32AI10V-1/E3-16AI20M-1/E3-16ISO20M-1/E3-16AI8AO-1/E3-8AO20M-1/E3-16ISOTC-1/E3-10RTD-1
Sixnet I/O Tool Kit 5.0.103
Red Lion Workbench 1.0.3
E2/E3 Address Table for Defining Transfers in Red Lion Workbench |
|||||
Model |
I/O Type |
Modbus Request Function Code |
Base Address |
Nb Items |
Comment |
E2/E3-MIX24880-D |
Discrete Input |
<2> Read Input Bits |
1 |
16 |
First 16 DI registers. |
E2/E3-MIX24880-D |
Analog Inputs |
<4> Read Input Registers |
8 |
16 |
Optional Count Registers for the first 16 DI Registers. |
E2/E3-MIX24880-D |
Discrete Input |
<2> Read Input Bits |
17 |
8 |
Optional. Last 8 DI registers are configurable as first 8 DO registers. |
E2/E3-MIX24880-D |
Discrete Outputs |
<15> Write Coil Bits |
1 |
8 |
Optional. Last 8 DI registers are configurable as first 8 DO registers. |
E2/E3-MIX24880-D |
Discrete Outputs |
<16> Write Holding Registers |
1 |
8 |
Optional. TPO Control Registers. |
E2/E3-MIX24882-D |
Discrete Outputs |
<16> Write Holding Registers |
3 |
8 |
Optional. TPO Control Registers. |
E2/E3-MIX24880-D |
Analog Inputs |
<4> Read Input Registers |
1 |
8 |
|
E2/E3-MIX24882-D |
Analog Outputs |
<16> Write Holding Registers |
1 |
2 |
|
E2/E3-MIX20884-D |
Discrete Input |
<2> Read Input Bits |
1 |
12 |
First 12 DI registers. |
E2/E3-MIX20884-D |
Analog Inputs |
<4> Read Input Registers |
8 |
12 |
Optional Count Registers for the first 12 DI Registers. |
E2/E3-MIX20884-D |
Discrete Input |
<2> Read Input Bits |
13 |
8 |
Optional. Last 8 DI registers are configurable as first 8 DO registers. |
E2/E3-MIX20884-D |
Discrete Outputs |
<15> Write Coil Bits |
1 |
8 |
Optional. Last 8 DI registers are configurable as first 8 DO registers. |
E2/E3-MIX20884 |
Analog Outputs |
<16> Write Holding Registers |
5 |
8 |
Optional. TPO Control Registers. |
E2/E3-MIX20884-D |
Analog Inputs |
<4> Read Input Registers |
1 |
8 |
|
E2/E3-MIX20884-D |
Analog Outputs |
<16> Write Holding Registers |
1 |
4 |
|
E2/E3-16DI24-D |
Discrete Input |
<2> Read Input Bits |
1 |
16 |
|
E2/E3-16DI24-D |
Analog Input |
<4> Read Input Registers |
1 |
16 |
Optional Count Registers |
E2/E3-16DO24-D |
Discrete Outputs |
<15> Write Coil Bits |
1 |
16 |
|
E2/E3-16DO24-D |
Analog Outputs |
<16> Write Holding Registers |
1 |
16 |
Optional TPO Registers |
E2/E3-32DI24-D |
Discrete Input |
<2> Read Input Bits |
1 |
32 |
|
E2/E3-32DI24-D |
Analog Input |
<4> Read Input Registers |
1 |
32 |
Optional Count Registers |
E2/E3-32DO24-D |
Discrete Input |
<15> Write Coil Bits |
1 |
32 |
|
E2/E3-32DO24-D |
Analog Outputs |
<16> Write Holding Registers |
1 |
32 |
Optional TPO Registers |
E2/E3-16AI20M-D |
Analog Inputs |
<4> Read Input Registers |
1 |
16 |
|
E2/E3-32AI20M-D |
Analog Inputs |
<4> Read Input Registers |
1 |
32 |
|
E2/E3-32AI10V-D |
Analog Inputs |
<4> Read Input Registers |
1 |
32 |
|
E2/E3-10RTD-D |
Analog Inputs |
<4> Read Input Registers |
1 |
10 |
|
E2/E3-8AO20M-D |
Analog Outputs |
<16> Write Holding Registers |
1 |
8 |
|
Diagnostic Bits (Common to all E2/E3 modules) |
Discrete Input |
<2> Read Input Bits |
33 |
32 |
Optional. See E2_Status_Bits.csv |
Importing Fieldbus configurations is very easy with Red Lion Workbench. The attached AllE2Modules.xml will import an example of 17 different models that can be used with E2 or E3 Modules. Once imported they can be duplicated or customized to fit a specific application. Once the configuration is customized it can be exported and reused in other applications.
E2/E3 configuration settings are imported from CSV files in three Levels. The first level imports the IP address, Port number and Protocol. The second level imports the Data type, Starting Address, Number of addresses and poll rate. The third level imports the tag names and off set number.
An example of all three levels are provided as attachments (Level1_Level2_Level3.zip). The attachments include an example of every E2/E3 model, datatypes and tag names. These attachments can be imported as is or be modified before they are imported. Below describes how to import them as is. The files are formatted as shown below.
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-432-9908.
For more information: http://www.redlion.net/support/policies-statements/warranty-statement