The AnybusŪ Communicator for EtherNet/IP and Modbus TCP allows the user to take almost any serial device and have it communicate to an EtherNet/IP or Modbus TCP network. The AnybusŪ Communicator is conformance tested to current Ethernet/IP/Modbus TCP specifications guaranteeing network compatibility. It acts as a device adapter on the network and presents the serial data to the master controller as easily processed I/O data.
Serial Applications
The AnybusŪ Communicator supports RS232, RS422 and RS485 serial electrical formats without any change in hardware. This allows for connectivity to a broad range of serial devices. Typical serial applications include variable frequency drives, sensors, actuators, human machine interfaces, barcode readers, RFID readers and industrial scales among others.
Configuration
No high level programming skills are needed to set up the AnybusŪ Communicator as configuration is accomplished using the free Windows-based Anybus Configuration Manager. This software can be used to configure serial master protocols such as Modbus or other query-response based protocols. Configuring a Modbus application is as simple as running the embedded Modbus Wizard in the ACM. The AnybusŪ Communicator can also be easily configured to consume or produce dynamic serial data strings.
Connect to any network
With a broad range of devices supported, the AnybusŪ Communicator for EtherNet/IP and Modbus TCP provides the user with one of the most comprehensive solutions for solving EtherNet/IP to serial connectivity. In order to optimize the user experience, HMS provides free worldwide technical support for all of its products.
Please contact your local sales office or distributor for more information.
| KEY FEATURES | |
![]() |
|
| 10/100 MBit twisted pair RJ45 connection | |
| Multi-drop to up to 31 nodes | |
| CE, UL & cUL marked | |
| TCP/IP settings configurable with web-page, Configuration Tool, DHCP, ARP or with DIP switches | |
| Modbus/TCP class 0, class 1 and partially class 2 slave functionality | |
| Transformer isolated Ethernet interface | |
| Email functionality (SMTP) | |
| User downloadable web pages through FTP server | |
| 1.4 Mbyte storage space on Flash disk | |
| Suport fot AnyBus IPconfig utility for easy TCP/IP set up | |
| Serial network configuration with ABC Config Tool | |
| SSI sripts used for easy display/control of process data on webpages | |
| DIN-rail mountable - PE via DIN-rail | |
| Anybus Configuration Manager for easy configuration | |
| EtherNet/IP Adapter Class Device |
| TECHNICAL SPECIFICATIONS | |
| Size: | 120 mm x 75 mm x 27 mm |
| Power Supply: | 24 VDC |
| Temperature: | 0 to +55°C |
| Current Consump: | Max 300 mA |
| Baud Rate: | 10/100 Mbit autodetect |
| Sub Baud Rate: | 1.2, 2.4, 4.8, 9.6, 19.2, 35.7, 38.4, 57,6 kbit/s |
| I/O Input: | 512 bytes |
| I/O Output: | 512 bytes |
| Mech Rating: | IP20 |
| Profile Support: | Modbus TCP Class 0, 1, and partial Class 2 server functionality, EtherNet/IP level 2 I/O Server CIP (ControlNet & DeviceNet) |
| Supp Features: | Modbus TCP, EtherNet/IP, Webserver, FTP, Email, DHCP, ARP, Telnet |
| Config Method: | Anybus Configuration Manager for Windows |
| Appl Interface: | RS232, RS422, RS485 |
| Flash disk size: | 1,4 Mbyte |
| Serial telegrams: | Max 100 different configurable telegrams |
| Modbus RTU commands: | Max 50 (request and response) |
| Included accessories: | CD with software and User Manuals, Configuration Cable RS232, DSUB with screw terminals for Sub-Network, Installation Leaflet. |
| Galvanic isolation: | Standard for both bus side and serial side |
| Alt. Order Code: | AB7028 (limited version with only Modbus-TCP + IT-functions) |
| Order Code: | AB7007 |